Command Signals: 4-20mA;
0-5VDC; 0-10VDC; potentiometer
Control Mode: Distributive Zero Cross; Phase Angle Firing
load
current
Zero Cross or Phase Angle Fire:
60, 90, 120,
180, 225,
350, 500,
650, 500,
800, 1000 or
1200 Amps
Line Voltage: 120, 240, 480, or 575 VAC; +10% -20% 50/60
Hz
Zero and Span: Factory pre-set. User adjustable over a
range of 20% of span.
Transient Voltage and dv/dt:
200 volts/microsecond minimum. Uses a dv/dt snubber and a metal
oxide varistor (MOV).
control
range
Zero Cross: 0 to 99.5% of line voltage
Phase Angle Firing: 0 to 97% of line voltage
linearity
Zero Cross: Linear with respect to the command signal
Phase Angle Firing: RMS load voltage is linear within 2%
of the command signal.
temperature
Operating: +32 to 122°F (0 to
+50°C)
Storage: 14 to +158°F
(-10 to +70°C)
Cooling: 60 amp convection, all
others fan cooled
Mounting: Panel mount with heat sink fins vertical
dimensions
60 through 225
Amp units:
16.25"H×9.5"W×9.25"D
350 through 500
Amp units:
14.75"H×20.125"W×8.5"D
600 amp units:
16.75"H×23"W×11.5"D
800 through 1200
amp units:
14.75"L×20.125"W×8.5"D
weight
60 through 225
Amp units:
22 lbs
350 through 500
Amp units:
24 lbs
600 amp units:
47 lbs
800 through 1200
amp units:
71 lbs |