TEMPCO Electric Heater Corporation |
Home | Product Lines | Temperature Control Hub | Back to (SCR) Introduction
|
|
|
|
|
||
| Command Signals:
4-20mA; 0-5VDC; 0-10VDC; potentiometer Control Mode: Distributive Zero Cross Load Current: 15, 25, 40 or 70 Amps Line Voltage: 208, 240, 277, 480, or 575 VAC; +10% to 20% 50/60 Hz Zero and Span: Factory pre-set. User adjustable over a range of 20% of span. Transient Voltage and dv/dt: 500 volts/microsecond minimum. Uses a dv/dt snubber and a metal oxide varistor (MOV). Control Range: 0 to 100% of line voltage |
Linearity: Average load
voltage is linear within 1% of the command signal. temperature Operating: +32 to 122°F (0 to +50°C) Storage: 14 to +158°F (-10 to +70°C) Cooling: Convection Mounting: Panel mount with heat sink fins vertical dimensions 10 to 40 Amp units: each assembly 9.215"H×6"W×3.1"D 70 Amp units: each assembly 17.25"H×10" W×5" D |
|
Potentiometer Kit (ordered separately): 5KW potentiometer and knob Part Number: SRS99001 Multi-Tap Transformer Input: 120/240V,
400V, 480V or 575V
|
||||||||||||
![]() |
| © Copyright 2008 Tempco Electric Heater Corporation. All Rights Reserved |
TEMPCO
Electric Heater Corporation *
607 North Central Avenue * Wood Dale, Illinois 60191 USA |