TEMPCO Electric Heater Corporation |
Home | Product Lines | Temperature Control Hub | Back to (SCR) Introduction
|
|
|
|
|
||
| Command Signals:
4-20mA; 0-5VDC; 0-10VDC; potentiometer Control Mode: Distributive Zero Cross Load Current per Leg: 60, 90, 120, 180, 225, 350, 500, 650, 800 1000 or 1200 Amps Line Voltage: 208, 240, 480, or 575 VAC; +10% to 20% 50/60 Hz Zero and Span: Factory pre-set. User adjustable over a range of 20% of span. Transient Voltage and dv/dt: 200 volts/microsecond minimum. Uses a dv/dt snubber and a metal oxide varistor (MOV). Control Range: 0 to 99.5% of line voltage Linearity: Average load voltage is linear within 2% of the command signal. |
temperature Operating: +32 to 122°F (0 to +50°C) Storage: 14 to +158°F (-10 to +70°C) Cooling: 60A convection; All others fan cooled Mounting: Panel mount with heat sink fins vertical
dimensions
weight |
|
|
|
||||||||||||||||||||
|
Potentiometer Kit (ordered separately): 5KW potentiometer and knob Part Number: SRS99001 |
|||||||||||||||||||||
![]() |
| © Copyright 2008 Tempco Electric Heater Corporation. All Rights Reserved |
TEMPCO
Electric Heater Corporation *
607 North Central Avenue * Wood Dale, Illinois 60191 USA |